Control Panel
RPS Menu Location
Panel Wide Parameters > SDI RPS/Enhanced Communication > RPS Port Number
3.13
Power Supervision
3.13.1
AC Fail Time
Default: 01:00
Selections: 00:01 to 90:00 (Minutes:Seconds)
This parameter sets the amount of time that the AC power must be off before the control
panel sends an AC Failure report.
Notice!
To comply with UL 864 requirements for Commercial Fire Systems, set this parameter to
1:00.
RPS Menu Location
Panel Wide Parameters > Power Supervision > AC Fail Time
3.13.2
Resend AC Fail
Default: No Reports
Selections:
–
–
–
This parameter sets the time interval that must pass without the AC failure event being
restored before the control panel re-sends the AC Failure report to the central station.
RPS Menu Location
Panel Wide Parameters > Power Supervision > Resend AC Fail
3.13.3
AC Fail Display
Default: 60
Selections: 10 to 300 (seconds) (increments of 5)
This parameter sets the amount of time in seconds the system waits before sounding a local
AC Failure annunciation.
Notice!
To comply with UL 864 requirements for Commercial Fire Systems, set this parameter within
10 to 200 seconds.
RPS Menu Location
Panel Wide Parameters > Power Supervision > AC Fail Display
3.13.4
AC Fail / Restoral Report
Default: No
Selections:
–
–
This parameter sends AC Power Supervision reports to the central station at the time
programmed for AC Fail Time.
Bosch Security Systems, Inc.
No Report -do not re-send AC Fail report.
After 6 Hours - e-send AC Fail report to central station after 6 hours of non-restoral.
After 12 Hours - re-send AC Fail report to central station after 12 hours of non-restoral.
Yes - end AC Fail and AC Restoral reports.
No - do not send AC Fail and AC Restoral reports.
Program Entry Guide
Panel Wide Parameters | en
2017.03 | 09 | F.01U.303.998
69