Fire Summary Sustain; Fire Supervision Event Type; Fire Trouble Resound - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
When an enclosure tamper event is processed, it is indicated on the keypads' displays and the
keypads sound a trouble tone. When the enclosure tamper has been restored, the control
panel automatically removes the tampered enclosure message from the keypads' displays and
the trouble tone is silenced if no other trouble events exist. While an enclosure tamper is
displayed at the keypad, the tamper event does not affect the arming or disarming process.
If installed and enabled, detects control panel door has been opened.
RPS Menu Location
Panel Wide Parameters > Miscellaneous > Enclosure Tamper Enable
3.15.7

Fire Summary Sustain

Default: Yes
Selections:
This parameter provides a continuous alarm output to keep fire or gas strobes active after the
fire or gas bell has stopped sounding.
RPS Menu Location
Panel Wide Parameters > Miscellaneous > Fire Summary Sustain
3.15.8

Fire Supervision Event Type

Default: 2 (Fire Supervision Restoral)
Selections:
This parameter determines how the control panel transmits a Fire Supervision Restoral event.
RPS Menu Location
Panel Wide Parameters > Miscellaneous > Fire Supervision Event Type
3.15.9

Fire Trouble Resound

Default: No Fire Trouble Resound
Selections:
This parameter determines if a fire or gas trouble event, although previously acknowledged
and silenced at a keypad, will automatically resound the trouble tone at 12:00 P.M., 12:00
A.M., or not at all if the point is still in an off-normal state.
A user's passcode must have an authority level of 1 or greater in an area to silence troubles.
Bosch Security Systems, Inc.
Yes - forces the Summary Fire and Summary Gas output to remain on after the Alarm
Silence command.
No - allows Summary Fire and Summary Gas output to activate when a corresponding
point in the system goes into alarm. This output provides a steady output until all
silenced fire or gas points in the system are returned to normal.
0 (Fire Trouble Restoral) - the control panel transmits a FIRE TROUBLE RESTORE when a
Fire Supervision point restores to normal.
1 (Fire Alarm Restoral) - the control panel transmits a FIRE ALARM RESTORE when a Fire
Supervision point restores to normal.
2 (Fire Supervision Restoral) - the control panel transmits a FIRE SUPERVISION RESTORE
when a Fire Supervision point restores to normal.
No Fire Trouble Resound - keypads will not re-sound the trouble tone.
Fire Trouble Resound @ 12:00 PM - keypads will re-sound the trouble tone at 12:00 P.M.
(noon) if any fire or gas point that falls within the scope of a keypad is in an off-normal
state.
Fire Trouble Resound @ 12:00 AM - keypads will re-sound the trouble tone at 12:00 A.M.
(midnight) if any fire or gas point that falls within the scope of a keypad is in an off-
normal state.
Program Entry Guide
Panel Wide Parameters | en