2.19.1.9 Settings

Addr.
Parameter
6101
Synchronizing
6102
SyncCB
6103
Vmin
6104
Vmax
6105
V<
6106
V>
6107
SYNC V1<V2>
6108
SYNC V1>V2<
6109
SYNC V1<V2<
6110A
Direct CO
6111A
TSUP VOLTAGE
6112
T-SYN. DURATION
6113A
25 Synchron
6120
T-CB close
6121
Balancing V1/V2
6122A
ANGLE ADJUSTM.
6123
CONNECTIONof V2
6125
VT Vn2, primary
6130
dV ASYN V2>V1
6131
dV ASYN V2<V1
6132
df ASYN f2>f1
6133
df ASYN f2<f1
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
Setting Options
ON
OFF
(Setting options depend
on configuration)
20 .. 125 V
20 .. 140 V
1 .. 60 V
20 .. 140 V
YES
NO
YES
NO
YES
NO
YES
NO
0.00 .. 60.00 sec
0.01 .. 1200.00 sec; ∞
YES
NO
0.01 .. 0.60 sec
0.50 .. 2.00
0 .. 360 °
A-G
B-G
C-G
A-B
B-C
C-A
0.10 .. 800.00 kV
0.5 .. 50.0 V
0.5 .. 50.0 V
0.01 .. 2.00 Hz
0.01 .. 2.00 Hz
2.19 Synchronism and Voltage Check 25 (7SJ64 only)
Default Setting
OFF
None
90 V
110 V
5 V
80 V
NO
NO
NO
NO
0.10 sec
30.00 sec
YES
0.06 sec
1.00
0 °
A-B
12.00 kV
2.0 V
2.0 V
0.10 Hz
0.10 Hz
Comments
Synchronizing Function
Synchronizable circuit breaker
Minimum voltage limit: Vmin
Maximum voltage limit: Vmax
Threshold V1, V2 without voltage
Threshold V1, V2 with voltage
ON-Command at V1< and V2>
ON-Command at V1> and V2<
ON-Command at V1< and V2<
Direct ON-Command
Supervision time of V1>;V2> or
V1<;V2<
Maximum duration of Synchroni-
zation
Switching at synchronous condi-
tion
Closing (operating) time of CB
Balancing factor V1/V2
Angle adjustment (transformer)
Connection of V2
VT nominal voltage V2, primary
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum frequency difference
f2>f1
Maximum frequency difference
f2<f1
298