Information List - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

Addr.
Parameter
1310
51N Drop-out
1311
51N IEC CURVE
1312
51N ANSI CURVE
1313A
MANUAL CLOSE
1314A
50N-2 active
1315A
50N T DROP-OUT
1330
50N/51N
1331
MofPU Res T/TEp
2201
INRUSH REST.
2202
2nd HARMONIC
2203
CROSS BLOCK
2204
CROSS BLK TIMER
2205
I Max

2.2.12 Information List

No.
Information
1704
>BLK 50/51
1714
>BLK 50N/51N
1721
>BLOCK 50-2
1722
>BLOCK 50-1
1723
>BLOCK 51
1724
>BLOCK 50N-2
1725
>BLOCK 50N-1
1726
>BLOCK 51N
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
C
Setting Options
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50N-2 instant.
50N-1 instant.
51N instant.
Inactive
Always
With 79 Active
0.00 .. 60.00 sec
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
OFF
ON
10 .. 45 %
NO
YES
0.00 .. 180.00 sec
1A
0.30 .. 25.00 A
5A
1.50 .. 125.00 A
Type of In-
formation
SP
>BLOCK 50/51
SP
>BLOCK 50N/51N
SP
>BLOCK 50-2
SP
>BLOCK 50-1
SP
>BLOCK 51
SP
>BLOCK 50N-2
SP
>BLOCK 50N-1
SP
>BLOCK 51N
2.2 Overcurrent Protection 50, 51, 50N, 51N
Default Setting
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
50N-2 instant.
Manual Close Mode
Always
50N-2 active
0.00 sec
50N Drop-Out Time Delay
50N/51N
Multiple of Pickup <->
T/TEp
OFF
Inrush Restraint
15 %
2nd. harmonic in % of fun-
damental
NO
Cross Block
0.00 sec
Cross Block Time
7.50 A
Maximum Current for
Inrush Restraint
37.50 A
Comments
Comments