Test Mode And Transmission Block; Checking The System (Scada) Interface - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

3 Mounting and Commissioning
3.3.1

Test Mode and Transmission Block

Activation and De-
activation
3.3.2

Checking the System (SCADA) Interface

Prefacing Remarks
421
WARNING!
Warning of dangers evolving from improper primary tests
Non-observance of the following measures can result in death, personal injury or sub-
stantial property damage.
Primary tests are only allowed to be carried out by qualified personnel, who are famil-
iar with the commissioning of protection systems, the operation of the plant and the
safety rules and regulations (switching, grounding, etc.).
If the device is connected to a central or main computer system via the SCADA inter-
face, then the information that is transmitted can be influenced. This is only possible
with some of the protocols available (see Table „Protocol-dependent functions" in the
Appendix A.6).
If Test mode is set ON, then a message sent by a SIPROTEC 4 device to the main
system has an additional test bit. This bit allows the message to be recognized as re-
sulting from testing and not an actual fault or power system event. Furthermore it can
be determined by activating the Transmission block that no annunciations at all are
transmitted via the system interface during test mode.
The SIPROTEC 4 System Description describes in detail how to activate and deacti-
vate test mode and blocked data transmission. Note that when DIGSI is being used,
the program must be in the Online operating mode for the test features to be used.
If the device features a system interface and uses it to communicate with the control
center, the DIGSI device operation can be used to test if messages are transmitted
correctly. This test option should however definitely not be used while the device is in
service on a live system.
DANGER!
Danger evolving from operating the equipment (e.g. circuit breakers, discon-
nectors) by means of the test function
Non-observance of the following measure will result in death, severe personal injury
or substantial property damage.
Equipment used to allow switching such as circuit breakers or disconnectors is to be
checked only during commissioning. Do not under any circumstances check them by
means of the test function during real operation by transmitting or receiving messages
via the system interface.
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents