Siemens siprotec SJ62 User Manual page 393

Multi-functional protective relay with local control
Table of Contents

Advertisement

3 Mounting and Commissioning
Pickup Voltages of
Binary Inputs BI8 to
BI20, BI25 to BI37
Bus Address
391
Table 3-16
Jumper settings for pickup voltages of the binary inputs BI8 to BI20 and BI25
to BI37 on the input/output board B–I/O-2
Binary Input
BI8
BI9
BI10
BI 11
BI12
BI13
BI14
BI15
BI16
BI17
BI18
BI19
BI20
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 220/250 VDC and 115/230 VAC
Jumpers X71, X72 and X73 on the B–I/O-2 board serve to set up the Bus Address.
The jumpers must not be changed. The following table lists the jumper presettings.
Table 3-17
Jumper Settings Input/Output Board B-I/O-2
Jumper
Mounting location
19
X71
1–2
X72
2–3
X73
2–3
Jumper
BI25
X21
BI26
X22
BI27
X23
BI28
X24
BI29
X25
BI30
X26
BI31
X27
BI32
X28
BI33
X29
BI34
X30
BI35
X31
BI36
X32
BI37
X33
1
Housing size
/
2
Mounting location
33
1–2
1–2
2–3
1)
19 VDC Pickup
88 VDC Pickup
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1
Housing size
Mounting
Mounting
location 33 (left)
location 19 (right)
1-2
2-3
2-3
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2)
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
/
1
1-2
1-2
2-3