2.1.3

Power System Data 1

2.1.3.1

Description

2.1.3.2

Setting Notes

General
Nominal Frequency
Phase Rotation Re-
versal
Temperature Unit
Polarity of Current
Transformers
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The device requires certain basic data regarding the protected equipment, so that the
device can adapt to its desired application. These may be, for instance, nominal power
system and transformer data, measured quantity polarities and their physical connec-
tions, breaker properties (where applicable) etc. There are also certain parameters
that are common to all functions, i.e. not associated with a specific protection, control
or monitoring function. The following section discusses these data.
This data can be entered directly on the device featuring an integrated or detached
operator panel for parameters 209 PHASE SEQ., 210 TMin TRIP CMD, 211 TMax
CLOSE CMD and 212 BkrClosed I MIN. Select the MAIN MENU by pressing the
MENU key. Press the ▼ key to select SETTINGS and the
tings selection. To obtain the Power System Data display, select the P.System Data
1 in the SETTINGS menu.
In DIGSI double-click on Settings to display the relevant selection. A dialog box will
open under the option P.System Data 1 with the tabs Power system, CTs, VTs and
Breaker where you can configure the individual parameters. Thus the following Sub-
sections are structured accordingly.
The rated system frequency is set at address 214 Rated Frequency. The factory
presetting in accordance with the model number must only be changed if the device
will be employed for a purpose other than that which was planned when ordering.
Address 209 PHASE SEQ. is used to change the default phase sequence (A B C for
clockwise rotation), if your power system permanently has an anti-clockwise phase se-
quence (A C B). A temporary reversal of rotation is also possible using binary inputs
(see Section 2.21.2).
Address 276 TEMP. UNIT allows you to display the temperature values either in
degree Celsius or in degree Fahrenheit.
At address 201 CT Starpoint, the polarity of the wye-connected current transform-
ers is specified (the following figure applies correspondingly for two current transform-
ers). This setting determines the measuring direction of the device (forwards = line di-
rection). Modifying this setting also results in a polarity reversal of the ground current
inputs I
or I
.
N
NS
2.1 General
key to navigate to the set-
44