Siemens siprotec SJ62 User Manual page 368

Multi-functional protective relay with local control
Table of Contents

Advertisement

Connection Exam-
ples for 7SJ63
Connection Exam-
ples for 7SJ64
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Connection examples for current and voltage transformer circuits are provided in Ap-
pendix A.3. The device can either be connected with three phase–ground voltages
(connection mode VT Connect. 3ph = Van, Vbn, Vcn), or with two phase–phase
voltages and V
(also called the displacement voltage) from open delta VTs as (con-
delta
nection mode VT Connect. 3ph = Vab, Vbc, VGnd). For the latter, only two
phase–phase voltages or the displacement voltage V
device settings the appropriate voltage connection must be entered under address
213, in P.System Data 1.
As the voltage inputs of the 7SJ63 device have an operating range from 0 to 170 V,
this means that phase-to-phase voltages can be assessed in connection of phase-to-
ground voltages up to √3 · 170 V = 294 V, in the latter case up to 170 V.
If there is only one voltage transformer on the system side, wiring is performed accord-
ing to examples on single-phase connection. For this case, address 240 VT
Connect. 1ph in the P.System Data 1 specifies to the device which primary
voltage is connected to which analog input.
Connection examples for current and voltage transformer circuits are provided in Ap-
pendix A.3.
For the normal connection the 4th voltage measuring input is not used. Correspond-
ingly the address 213 must be set to VT Connect. 3ph = Van, Vbn, Vcn. The
factor in address 206Vph / Vdelta must however be set to 1.73 (this factor is used
internally for the conversion of measurement and fault recording values).
Also an additional connection example of an e-n-winding of the voltage transformer is
shown. Here address 213 must be set to VT Connect. 3ph = Van,Vbn,Vcn,VGn.
The factor address 206 Vph / Vdelta depends on the transformation ratio of the
e–n-winding. For additional hints, please refer to section 2.1.3.2 under „Transforma-
tion Ratio".
Another figure shows an example of a connection of the e–n winding of a set of voltage
transformers, in this case, however of a central set of transformers at a busbar. For
more information refer to the previous paragraph.
Another figure shows an example of the connection of a different voltage, in this case
the busbar voltage (e.g. for the synchronization function). For the synchronization
function address 213 must be set to VT Connect. 3ph = Van,Vbn,Vcn,VGn.
Balancing V1/V2, address 6X21 is always equal to 1 unless the feeder VT and bus-
barside VT have a different transformation ratio. The factor in address 206Vph /
Vdelta must however be set to 1.73 (this factor is used internally for the conversion
of measurement and fault recording values).
Also two phase–phase voltages or the displacement voltage V
to the device. Here address 213 must be set to VT Connect. 3ph = Vab, Vbc,
VGnd. For the latter, only two phase–phase voltages or the displacement voltage V
can be connected.
As the voltage inputs of the 7SJ64 device have an operating range from 0 to 200 V,
this means that when connecting to the device phase-to-ground voltages, the phase-
to-phase voltages can be assessed up to √3 · 200 V = 346 V, with connection of phase-
to-phase voltages up to 200 V.
If there is only one voltage transformer on the system side, wiring is performed accord-
ing to examples on single-phase connection. For this case, address 240 VT
Connect. 1ph in the P.System Data 1 specifies to the device which primary
voltage is connected to which analog input.
3.1 Mounting and Connections
can be connected. In the
delta
can be connected
delta
delta
366

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents