Information List - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

Addr.
Parameter
1905
51Nc PICKUP
1906
51Nc T-DIAL
1907
51Nc T-DIAL
2001
67c-2 PICKUP
2002
67c-2 DELAY
2003
67c-1 PICKUP
2004
67c-1 DELAY
2005
67c-TOC PICKUP
2006
67c-TOC T-DIAL
2007
67c-TOC T-DIAL
2101
67Nc-2 PICKUP
2102
67Nc-2 DELAY
2103
67Nc-1 PICKUP
2104
67Nc-1 DELAY
2105
67Nc-TOC PICKUP
2106
67Nc-TOC T-DIAL
2107
67Nc-TOC T-DIAL
2.4.4

Information List

No.
Information
1730
>BLOCK CLP
1731
>BLK CLP stpTim
1732
>ACTIVATE CLP
1994
CLP OFF
1995
CLP BLOCKED
1996
CLP running
1997
Dyn set. ACTIVE
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
C
Setting Options
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
0.10 .. 35.00 A; ∞
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
0.10 .. 35.00 A; ∞
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
0.05 .. 35.00 A; ∞
1A
0.25 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
0.05 .. 35.00 A; ∞
1A
0.25 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
Type of In-
formation
SP
>BLOCK Cold-Load-Pickup
SP
>BLOCK Cold-Load-Pickup stop timer
SP
>ACTIVATE Cold-Load-Pickup
OUT
Cold-Load-Pickup switched OFF
OUT
Cold-Load-Pickup is BLOCKED
OUT
Cold-Load-Pickup is RUNNING
OUT
Dynamic settings are ACTIVE
2.4 Dynamic Cold Load Pickup
Default Setting
1.00 A
51Nc Pickup
5.00 A
0.50 sec
51Nc Time Dial
5.00
51Nc Time Dial
10.00 A
67c-2 Pickup
50.00 A
0.00 sec
67c-2 Time Delay
2.00 A
67c-1 Pickup
10.00 A
0.30 sec
67c-1 Time Delay
1.50 A
67c Pickup
7.50 A
0.50 sec
67c Time Dial
5.00
67c Time Dial
7.00 A
67Nc-2 Pickup
35.00 A
0.00 sec
67Nc-2 Time Delay
1.50 A
67Nc-1 Pickup
7.50 A
0.30 sec
67Nc-1 Time Delay
1.00 A
67Nc-TOC Pickup
5.00 A
0.50 sec
67Nc-TOC Time Dial
5.00
67Nc-TOC Time Dial
Comments
Comments
122

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents