Settings - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions

2.3.11 Settings

Addr.
Parameter
1501
FCT 67/67-TOC
1502
67-2 PICKUP
1503
67-2 DELAY
1504
67-1 PICKUP
1505
67-1 DELAY
1507
67-TOC PICKUP
1508
67 TIME DIAL
1509
67 TIME DIAL
1510
67-TOC Drop-out
1511
67- IEC CURVE
1512
67- ANSI CURVE
1513A
MANUAL CLOSE
1514A
67 active
1516
67 Direction
1518A
67 T DROP-OUT
1519A
ROTATION ANGLE
1530
67
113
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
C
Setting Options
OFF
ON
0.10 .. 35.00 A; ∞
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
0.10 .. 35.00 A; ∞
1A
0.50 .. 175.00 A; ∞
5A
0.00 .. 60.00 sec; ∞
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.50 .. 15.00 ; ∞
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
67-2 instant.
67-1 instant.
67-TOC instant.
Inactive
with 79 active
always
Forward
Reverse
0.00 .. 60.00 sec
-180 .. 180 °
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
Default Setting
OFF
67, 67-TOC Phase Time
Overcurrent
2.00 A
67-2 Pickup
10.00 A
0.10 sec
67-2 Time Delay
1.00 A
67-1 Pickup
5.00 A
0.50 sec
67-1Time Delay
1.00 A
67-TOC Pickup
5.00 A
0.50 sec
67-TOC Time Dial
5.00
67-TOC Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve
67-2 instant.
Manual Close Mode
always
67 active
Forward
Phase Direction
0.00 sec
67 Drop-Out Time Delay
45 °
Rotation Angle of Refer-
ence Voltage
67
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Comments