Siemens siprotec SJ62 User Manual page 426

Multi-functional protective relay with local control
Table of Contents

Advertisement

Structure of the
Test Dialog Box
Changing the Oper-
ating State
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The hardware test can be carried out using DIGSI in the Online operating mode:
• Open the Online directory by double-clicking; the operating functions for the device
appear.
• Click on Test; the function selection appears in the right half of the screen.
• Double-click in the list view on Hardware Test. The dialog box of the same name
opens (see the following figure).
The dialog box is classified into three groups: BI for binary inputs, REL for output
relays, and LED for light-emitting diodes. On the left of each of these groups is an ac-
cordingly labelled button. By double-clicking a button, information regarding the asso-
ciated group can be shown or hidden.
In the column Status the present (physical) state of the hardware component is dis-
played. Indication is made by symbols. The physical actual states of the binary inputs
and outputs are indicated by an open or closed switch symbol, the LEDs by a dark or
illuminated LED symbol.
The opposite state of each element is displayed in the column Scheduled. The display
is made in plain text.
The right-most column indicates the commands or messages that are configured
(masked) to the hardware components.
Figure 3-35
Test of the binary inputs and outputs — example
To change the condition of a hardware component, click on the associated button in
the Scheduled column.
Password No. 6 (if activated during configuration) will be requested before the first
hardware modification is allowed. After entry of the correct password a condition
change will be executed. Further condition changes remain possible while the dialog
box is open.
3.3 Commissioning
424