6.5.8

Settings Group Switching

For different applications and operation, cases require different function settings. In a settings group, the user
can set the settings specifically for an operating case.
All 7SR5 devices support up to 4 independent settings groups.
Group number (Gn) 1 to 4.
At any 1 time only 1 group of settings can be active.
The user can save the respective function settings in so-called Settings groups and, if necessary, activate them
quickly. In the process, only one settings group is active at any given time. During operation, the user can
switch between settings groups. The source of the switchover can be selected via a parameter.
Switchover of the settings groups can be done via the following alternatives:
Via the front fascia LCD display menu directly on the device
Via an online PC connection to the device via Reydisp Manager 2
Via binary inputs
Via communication connection to a substation automation technology
The communication protocols IEC 60870-5-103, IEC 61850, DNP3, Modbus RTU, and Modbus TCP can be used
for switching the settings groups.
A settings group includes all switchable settings of the device. Except for a few exceptions (for example,
general device settings such as rated frequency), all device settings can be switched.
[sc_7SR5_SettingsGroupsReydisp, 1, --_--]
Figure 6-12

Changing Setting Group via Device Display

6.5.9
To reach the Setting Group menu, proceed via Main Menu > Settings > Configuration > Device.
Select Active Group to activate one of the setting groups (1 to 4).
Select View/Edit Group to edit 1 group while the relay operates in accordance with settings from another
active group using.
Press the Enter button to change group number, then by using ▲,▼ buttons select the group.
The device is informed about a settings group change process from the display.
Reyrolle 7SR5, Operating, Manual
C53000-B7040-C013-1, Edition 05.2021
Settings Group via Reydisp Manager 2
Commissioning
6.5 Device Configuration
93