SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Note
After termination of the system interface test the device will reboot. Thereby, all annun-
ciation buffers are erased. If required, these buffers should be extracted with DIGSI
prior to the test.
The interface test is carried out using DIGSI in the Online operating mode:
• Open the Online directory by double-clicking; the operating functions for the device
appear.
• Click on Test; the function selection appears in the right half of the screen.
• Double-click on Generate Annunciations shown in the list view. The dialog box
Generate Annunciations opens (refer to the following figure).
In the column Indication the display texts of all indications are displayed which were
allocated to the system interface in the matrix. In the column SETPOINT Status the
user has to define the value for the messages to be tested. Depending on annuncia-
tion type, several input fields are offered (e.g. message „ON" / message „OFF"). By
clicking on one of the fields you can select the desired value from the pull-down menu.
Figure 3-34
System interface test with dialog box: Generate annunciations — example
When clicking one of the buttons in the column Action for the first time, you will be
prompted for the password no. 6 (for hardware test menus). After correct entry of the
password, individual annunciations can be initiated. To do so, click on the button Send
on the corresponding line. The corresponding message is issued and can be read out
either from the event log of the SIPROTEC 4 device or from the substation control
system.
As long as the window is open, further tests can be performed.
3.3 Commissioning
422