2 Functions
Monitoring
Voltage phase se-
quence
Current phase se-
quence
Fuse Failure Monitor
Trip circuit monitoring
Calibration data fault
Group Alarms
199
Possible Causes
External (power system or
connection)
External (power system or
connection)
External (voltage transform-
ers)
External (trip circuit or
control voltage)
Internal (hardware)
1)
After three unsuccessful restarts, the device is taken out of service.
2)
DOK = "Device Okay" = Ready for service relay drops off, protection and control function are
blocked.
Certain messages of the monitoring functions are already combined to group alarms.
A listing of the group alarms and their composition is given in the Appendix A.10. In
this case, it must be noted that message 160 „Alarm Sum Event" is only issued
when the measured value monitoring functions (8101 MEASURE. SUPERV) are
switched on.
Malfunction
Response
Annunciation
„Fail Ph. Seq. V" (176)
Annunciation
„Fail Ph. Seq. I" (175)
Annunciation
„VT FuseFail>10s" (169)
„VT FuseFail" (170)
Annunciation
„74TC Trip cir." (6865)
Annunciation
„Alarm NO calibr" (193) As allocated
Message (No.)
As allocated
As allocated
As allocated
As allocated
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015