3 Mounting and Commissioning
Power Supply
Live Status Contact
Pickup Voltages of
BI1 to BI7
385
There is no 230 V AC power supply available for 7SJ63.../DD
Table 3-8
Jumper settings for the nominal voltage of the integrated power supply on the
processor board B–CPU for 7SJ63.../DD
Jumper
60 to 125 V DC
X51
1-2
X52
1-2 and 3-4
X53
1-2
Table 3-9
Jumper setting for the quiescent state of the life contact on the processor
printed circuit board B-CPU for devices 7SJ63.../DD
Jumper
Open in the quiescent
X40
Table 3-10
Jumper settings for pickup voltages of binary inputs BI1 to BI7 on the proces-
sor printed circuit board B–CPU for 7SJ63.../DD
Binary Inputs
BI1
BI2
BI3
BI4
BI5
BI6
BI7
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 220 VDC and 115 VAC
Nominal Voltage
110 to 250 VDC, 115 VAC
2-3
2-3
2-3
interchangeable
Closed in the quiescent
state
1-2
Jumper
19 VDC Pickup
X21
X22
X23
X24
X25
X26
X27
24/48 VDC
Jumpers X51 to X53 are not
used
cannot be changed
Presetting
state
2-3
1)
88 VDC Pickup
L
L
L
L
L
L
L
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2-3
2)
H
H
H
H
H
H
H