Vibration and Shock Stress During Transport
4.1.7

Climatic Stress Tests

1
Temperatures
)
Humidity
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Standards:
Oscillation
IEC 60255-21-1, Class II;
IEC 60068-2-6
Shock
IEC 60255-21-2, Class I;
IEC 60068-2-27
Continuous Shock
IEC 60255-21-2, Class I;
IEC 60068-2-29
Standards:
Type tested (acc. IEC 60086-2-1 and -2, Test
Bd, for 16 h)
Permissible temporary operating tempera-
ture (tested for 96 h)
Recommended for permanent operation (ac-
cording to IEC 60255-6)
Limiting Temperatures for Storage
Limiting temperatures for transport
STORE AND TRANSPORT THE DEVICE WITH FACTORY PACKAGING.
1
) UL–certified according to Standard 508 (Industrial Control Equipment):
Limiting temperatures for normal operation
(i.e. output relays not energized)
Limiting temperatures with maximum load
(max. cont. permissible energization of
inputs and outputs)
Permissible humidity
Siemens recommends that all devices be installed such that they are not exposed to direct sun-
light, nor subject to large fluctuations in temperature that may cause condensation to occur.
4.1 General Device Data
IEC 60255-21 and IEC 60068
Sinusoidal
5 Hz to 8 Hz: ±7.5 mm amplitude;
8 Hz to 150 Hz: 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 orthogonal axes
Semi-sinusoidal
15 g acceleration, duration 11 ms,
each 3 shocks (in both directions of the 3 axes)
Semi-sinusoidal
10 g acceleration, duration 16 ms,
each 1000 shocks (in both directions of the 3
axes)
IEC 60255-6
–13 °F to +185 °F or -25.00 °C to +85 °C
– 4.00 °F to +158 °F or –20 °C to +70 °C (legibil-
ity of display may be restricted from +131 °F or
+55 °C)
+23 °F to +131 °F or -5 °C to +55 °C
–13 °F to +131 °F or -25 °C to +55 °C
–13 °F to +158 °F or -25 °C to +70 °C
–4 °F to +158 °F or -20 °C to +70 °C
+23 °F to +131 °F or –5 °C to +55 °C for 7SJ62
+23 °F to +104 °F or –5 °C to +40 °C for
7SJ63/64
Mean value per year ≤ 75 % relative humidity;
on 56 days of the year up to 93 % relative hu-
midity; condensation must be avoided!