Siemens siprotec SJ62 User Manual page 464

Multi-functional protective relay with local control
Table of Contents

Advertisement

Dropout Time Characteristics with Disk Emulation acc. to IEC
Dropout Setting
Tolerances
Influencing Variables for Pickup and Dropout
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Ass. to IEC 60255-3 or BS 142, Section 3.5.2 (see also Figures 4-1 and 4-2)
The dropout time curves apply for the range 0.05 ≤ (I/Ip) ≤ 0.90
For zero-sequence current read 3I0p instead of I
for ground fault read I
instead of I
Ep
IEC without Disk Emulation
IEC with Disk Emulation
Pickup/dropout thresholds I
Pickup time for 2 ≤ I/I
≤ 20
p
≤ 0.90
Dropout ratio for I/I
p
Power supply direct voltage in range 0.8 ≤
≤ 1.15
V
/V
PS
PSNom
Temperature in range
23.00 °F (–5 °C) ≤ Θ
≤ 131.00 °F (55 °C)
amb
Frequency in range 0.95 ≤ f/f
4.3 Inverse Time Overcurrent Protection 51, 51N
and T
p
and T
instead of T
p
IEp
approx. 1.05 · set value I
corresponds to approx. 0.95 · pickup threshold
approx. 0.90 · set value I
, I
2 % of set value or 10 mA for I
p
Ep
or 50 mA for I
5 % of reference (calculated) value + 2 %
current tolerance, respectively 30 ms
5 % of reference (calculated) value + 2 %
current tolerance, respectively 30 ms
1 %
0.5 %/10 K
≤ 1.05
1 %
Nom
instead of T
;
3I0p
p
p
for I
/I
p
p
Nom
p
Nom
= 5 A
Nom
≥ 0.3,
= 1 A
462