A Appendix
Addr.
Parameter
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7137
Cmd.via control
7138
Internal SYNC
7139
External SYNC
7140
ZONE SEQ.COORD.
7150
50-1
7151
50N-1
7152
50-2
7153
50N-2
7154
51
7155
51N
7156
67-1
7157
67N-1
7158
67-2
7159
67N-2
7160
67 TOC
7161
67N TOC
7162
sens Ground Flt
7163
46
7164
BINARY INPUT
7165
3Pol.PICKUP BLK
657
Function
C
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0 .. 9
79M Auto Recl.
0 .. 9
79M Auto Recl.
(Setting options depend
on configuration)
79M Auto Recl.
(Setting options depend
on configuration)
79M Auto Recl.
YES
NO
79M Auto Recl.
OFF
ON
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
YES
NO
Setting Options
Default Setting
0.50 sec
0.50 sec
0.50 sec
0.50 sec
0.50 sec
0.50 sec
0.50 sec
0.50 sec
1
1
None
None
NO
OFF
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
No influence
NO
Comments
Dead Time 1: Phase Fault
Dead Time 1: Ground Fault
Dead Time 2: Phase Fault
Dead Time 2: Ground Fault
Dead Time 3: Phase Fault
Dead Time 3: Ground Fault
Dead Time 4: Phase Fault
Dead Time 4: Ground Fault
Number of Reclosing Cycles
Ground
Number of Reclosing Cycles
Phase
Close command via control
device
Internal 25 synchronisation
External 25 synchronisation
ZSC - Zone sequence coordina-
tion
50-1
50N-1
50-2
50N-2
51
51N
67-1
67N-1
67-2
67N-2
67 TOC
67N TOC
(Sensitive) Ground Fault
46
Binary Input
3 Pole Pickup blocks 79
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015