Siemens siprotec SJ62 User Manual page 662

Multi-functional protective relay with local control
Table of Contents

Advertisement

Addr.
Parameter
7246
bef.4.Cy:67 TOC
7247
bef.4.Cy:67NTOC
8001
START
8101
MEASURE. SUPERV
8102
BALANCE V-LIMIT
8103
BAL. FACTOR V
8104
BALANCE I LIMIT
8105
BAL. FACTOR I
Σ I THRESHOLD
8106
Σ I FACTOR
8107
8201
FCT 74TC
8301
DMD Interval
8302
DMD Sync.Time
8311
MinMax cycRESET
8312
MiMa RESET TIME
8313
MiMa RESETCYCLE
8314
MinMaxRES.START
8315
MeterResolution
9011A
RTD 1 TYPE
9012A
RTD 1 LOCATION
9013
RTD 1 STAGE 1
9014
RTD 1 STAGE 1
9015
RTD 1 STAGE 2
9016
RTD 1 STAGE 2
9021A
RTD 2 TYPE
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Function
C
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=∞
Fault Locator
Pickup
TRIP
Measurem.Superv
OFF
ON
Measurem.Superv
10 .. 100 V
Measurem.Superv
0.58 .. 0.90
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
0.05 .. 2.00 A; ∞
Measurem.Superv
1A
0.25 .. 10.00 A; ∞
5A
Measurem.Superv
0.00 .. 0.95
74TC TripCirc.
ON
OFF
Demand meter
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
Demand meter
On The Hour
15 After Hour
30 After Hour
45 After Hour
Min/Max meter
NO
YES
Min/Max meter
0 .. 1439 min
Min/Max meter
1 .. 365 Days
Min/Max meter
1 .. 365 Days
Energy
Standard
Factor 10
Factor 100
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Setting Options
Default Setting
Set value T=T
Set value T=T
Pickup
ON
50 V
0.75
0.50 A
2.50 A
0.50
0.10 A
0.50 A
0.10
ON
60 Min., 1 Sub
On The Hour
YES
0 min
7 Days
1 Days
Standard
Pt 100 Ω
Oil
100 °C
212 °F
120 °C
248 °F
Not connected
A.8 Settings
Comments
before 4. Cycle: 67 TOC
before 4. Cycle: 67N TOC
Start fault locator with
Measurement Supervision
Voltage Threshold for Balance
Monitoring
Balance Factor for Voltage
Monitor
Current Threshold for Balance
Monitoring
Balance Factor for Current
Monitor
Summated Current Monitoring
Threshold
Summated Current Monitoring
Factor
74TC TRIP Circuit Supervision
Demand Calculation Intervals
Demand Synchronization Time
Automatic Cyclic Reset Function
MinMax Reset Timer
MinMax Reset Cycle Period
MinMax Start Reset Cycle in
Meter resolution
RTD 1: Type
RTD 1: Location
RTD 1: Temperature Stage 1
Pickup
RTD 1: Temperature Stage 1
Pickup
RTD 1: Temperature Stage 2
Pickup
RTD 1: Temperature Stage 2
Pickup
RTD 2: Type
660