2.17.3 Settings

Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
CURRENT
0
VOLTAGE
0
POWER
0
VOLTAGE SYSTEM
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
Setting Options
OFF
ON
Alarm Only
3-phase
1-phase
no reference
Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
df/dt rising
df/dt falling
Binray Input
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Exceeding
Dropping below
Ia
Ib
Ic
In
In sensitive
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
Ia Va-n
Ib Vb-n
Ic Vc-n
Phase-Phase
Phase-Earth
0.05 .. 35.00 A
0.05 .. 35.00 A
0.001 .. 1.500 A
2.17 Flexible Protection Functions (7SJ64 only)
Default Setting
OFF
Flexible Function
3-phase
Mode of Operation
Please select
Selection of Measured Quantity
Fundamental
Selection of Measurement
Method
Exceeding
Pickup with
Ia
Current
Please select
Voltage
Ia Va-n
Power
Phase-Phase
Voltage System
2.00 A
Pickup Threshold
2.00 A
Pickup Threshold
0.100 A
Pickup Threshold
Comments
272

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64