Table 32: Sample Power Requirements For An Srx5800 Services Gateway Scb2 - Juniper SRX5800 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5800:
Table of Contents

Advertisement

Table 32: Sample Power Requirements for an SRX5800 Services Gateway SCB2 and RE2
Chassis Component
Part Number
Base system
SRX5800BASE-HC-AC
High-capacity cooling
SRX5800-HC-FAN
system
SPC - slots 0 through
SPC2
4
See note below.
MPC - slot 5
IOC2 with two MICs
SCB 0 (slot 6 for Zone
SCB2 with RE2
1)
SCB 1 (slot 7 for Zone
SCB2
0)
MPC - slot 8
IOC2 with two MICs
SPC - slots 9 through
SPC2
13
See note below.
Total power requirement
Copyright © 2015, Juniper Networks, Inc.
Calculate the power requirements (usage) as shown in
1.
For the power consumption specifications of specific SRX5800 services gateway
cards, see the
SRX5400, SRX5600, and SRX5800 Services Gateway Card Guide
www.juniper.net/techpubs/
Evaluate the power budget, including the budget for each zone, if applicable. In this
2.
step, we check the required power against the maximum output power of available
power supply options.
Table 33 on page 114
lists the power supplies, their maximum output power, and unused
power (or a power deficit).
Power
Requirement
Zone 0 Power
50 W
25 W
320 W * 2 = 640 W
320 W
585 W * 5= 2925 W
570 W
200 W
90 W
200 W
200 W
570 W
570 W
585 W * 5 = 2925 W
2925 W
SRX5800
Zone 0 total: 4040
standard-capacity
W
AC (not zoned) 8170
W
.
Chapter 7: Planning and Preparing the Site
Table 32 on page
113.
Zone 1 Power
25 W
320 W
2925 W
570 W
290 W
Zone 1 total: 4130 W