Table 36: Sample Power Requirements For An Srx5800 Services Gateway - Juniper SRX5800 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5800:
Table of Contents

Advertisement

Table 36: Sample Power Requirements for an SRX5800 Services Gateway SCB3, IOC3, and
RE2
Chassis Component
Part Number
Base system
SRX5800BASE-HC-AC
High-capacity cooling
SRX5800-HC-FAN
system
SPC - slots 0 through
SPC2
4
See note below.
MPC - slot 5
IOC3
SCB 0 (slot 6 for Zone
SCB3 with RE2
1)
SCB 1 (slot 7 for Zone
SCB3
0)
MPC - slot 8
IOC3
SPC - slots 9 through
SPC2
13
See note below.
Total power requirement
Copyright © 2015, Juniper Networks, Inc.
Calculate the power requirements (usage) as shown in
1.
For the power consumption specifications of specific SRX5800 services gateway
cards, see the
SRX5400, SRX5600, and SRX5800 Services Gateway Card Guide
www.juniper.net/techpubs/
Evaluate the power budget, including the budget for each zone, if applicable. In this
2.
step, we check the required power against the maximum output power of available
power supply options.
Table 37 on page 118
lists the power supplies, their maximum output power, and unused
power (or a power deficit).
Power
Requirement
Zone 0 Power
50 W
25 W
320 W * 2 = 640 W
320 W
585 W * 5= 2925 W
607 W
300 W
90 W
300 W
300 W
607 W
607 W
585 W * 5 = 2925 W
2925 W
SRX5800
Zone 0 total: 4177 W
standard-capacity
AC (not zoned) 8444
W
.
Chapter 7: Planning and Preparing the Site
Table 36 on page
117.
Zone 1 Power
25 W
320 W
2925 W
607 W
390 W
Zone 1 total: 4267 W
at
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents