SRX5800 Services Gateway Hardware Guide
Table 45: Power System Electrical Specifications
Item
Redundancy
Output power (maximum) per supply
Output power (maximum) per system
Related
Documentation
DC Power Cable Specifications for the SRX5800 Services Gateway
Related
Documentation
136
Table 45 on page 136
lists the power system electrical specifications.
Normal-Capacity
2+2
2800 W
5600 W
Calculating Power Requirements for the SRX5800 Services Gateway on page 107
DC Power Circuit Breaker Requirements for the SRX5800 Services Gateway on page 137
DC Power Source Cabling for the SRX5800 Services Gateway on page 138
DC Power Cable Specifications for the SRX5800 Services Gateway on page 136
DC Power Cable Lug Specifications for the SRX5800 Services Gateway on page 137
Table 46 on page 136
summarizes the specifications for the power cables, which you must
supply.
Table 46: DC Power Cable Specifications
Cable Type
Power
CAUTION:
You must ensure that power connections maintain the proper
polarity. The power source cables might be labeled
their polarity. There is no standard color coding for DC power cables. The
color coding used by the external DC power source at your site determines
the color coding for the leads on the power cables that attach to the terminal
studs on each power supply.
SRX5800 Services Gateway DC Power Supply Specifications on page 135
Calculating Power Requirements for the SRX5800 Services Gateway on page 107
DC Power Circuit Breaker Requirements for the SRX5800 Services Gateway on page 137
DC Power Source Cabling for the SRX5800 Services Gateway on page 138
High-Capacity
2+2
Two-feed mode
4100 W
8200 W
Quantity and Specification
2
Eight 6-AWG (13.3 mm
), minimum 60°C wire, or as required by the
local code
One-feed mode
1700 W
3400 W
and
to indicate
(+)
(–)
Copyright © 2015, Juniper Networks, Inc.