CHAPTER 10

Grounding Specifications

SRX5800 Services Gateway Chassis Grounding Point Specifications

Copyright © 2015, Juniper Networks, Inc.
SRX5800 Services Gateway Chassis Grounding Point Specifications on page 127
SRX5800 Services Gateway Grounding Cable Specifications on page 128
SRX5800 Services Gateway Grounding-Cable Lug Specification on page 129
WARNING:
To meet safety and electromagnetic interference (EMI)
requirements and to ensure proper operation, you must properly ground the
services gateway chassis before connecting power. See
SRX5800 Services Gateway" on page 220
CAUTION:
Before services gateway installation begins, a licensed electrician
must attach cable lugs to the grounding and power cables that you supply.
A cable with an incorrectly attached lug can damage the services gateway.
The services gateway chassis has two grounding points along the lower edge of the back
panel. Each grounding point consists of two threaded holes spaced 0.625-in. (15.86-mm)
apart (see
Figure 68 on page
and the right grounding point fits UNC 1/4–20 screws (American). The accessory box
shipped with the services gateway includes the cable lug that attaches to the grounding
cable and two UNC 1/4–20 screws used to secure the grounding cable to the right-side
grounding point on the services gateway.
for instructions.
128). The left grounding point fits M6 screws (European),
"Grounding the