Power Supply Efficiency
~88 %
86 %
1
These values are at full load and nominal voltage.
Calculate thermal output (BTUs) for the system. To calculate this value, add the total
4.
input power requirement (in watts) for the two zones together and multiply the sum
by 3.41 as shown in
Table 39 on page 119
Thermal Output (BTUs per hour)
(4764 + 4849) * 3.41 = 32,780 BTU/hr
(4857 + 4962) * 3.41 = 33,482 BTU/hr
SRX5800 Services Gateway AC Power Supply Specifications on page 131
SRX5800 Services Gateway DC Power Supply Specifications on page 135
Chapter 7: Planning and Preparing the Site
1
Input Power Requirement
Zone 0: 4177/0.88= 4764 W
Zone 1: 4267/0.88= 4849 W
Zone 0: 4177/0.86= 4857 W
Zone 1: 4267/0.86= 4962 W
.