Table 30: Calculating Input Power for SRX5800 Services Gateway with SCB1 and RE1
Power Supply
SRX5800 AC high-capacity
SRX5800 DC high-capacity
Table 31: Calculating Thermal Output for SRX5800 Services Gateway with SCB1 and RE1
Power Supply
SRX5800 AC high-capacity
SRX5800 DC high-capacity
Copyright © 2015, Juniper Networks, Inc.
Power Supply Efficiency
~88 %
86 %
1
These values are at full load and nominal voltage.
Calculate thermal output (BTUs) for the system. To calculate this value, add the total
4.
input power requirement (in watts) for the two zones together and multiply the sum
by 3.41 as shown in
Table 31 on page
Thermal Output (BTUs per hour)
(4534 + 4636) * 3.41 = 31,269 BTU/hr
(4639 + 4744) * 3.41 = 31,996 BTU/hr
Chapter 7: Planning and Preparing the Site
1
Input Power Requirement
Zone 0: 3990/0.88= 4534 W
Zone 1: 4080/0.88= 4636 W
Zone 0: 3990/0.86= 4639 W
Zone 1: 4080/0.86= 4744 W