Srx5800 Services Gateway Environmental Specifications; Table 26: Services Gateway Environmental Specifications - Juniper SRX5800 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5800:
Table of Contents

Advertisement

SRX5800 Services Gateway Hardware Guide

SRX5800 Services Gateway Environmental Specifications

Related
Documentation
106
Table 26 on page 106
specifies the environmental specifications required for normal
services gateway operation. In addition, the site should be as dust-free as possible.

Table 26: Services Gateway Environmental Specifications

Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the services gateway only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110-16,
110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
SRX5800 Services Gateway Agency Approvals on page 439
SRX5800 Services Gateway General Safety Guidelines and Warnings on page 399
SRX5800 Services Gateway Fire Safety Requirements and Fire Suppression Equipment
on page 407
SRX5800 Services Gateway Definition of Safety Warning Levels on page 397
General Electrical Safety Guidelines and Warnings on page 427
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping crate: –40°F (–40°C)
to 158°F (70°C)
Tested to meet Telcordia Technologies Zone 4 earthquake
requirements
AC power: 20,160, BTU/hour (5912 W)
DC power: 17,057 BTU/hour (5002 W)
NOTE:
These specifications are estimates and subject to change.
Copyright © 2015, Juniper Networks, Inc.