Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace microprocessor n. (n = microprocessor number)
• 80070301-1101ffff : Sensor [SensorElementName] has transitioned to non-recoverable from a less
severe state. (PCI 1 Temp)
This message is for the use case when an implementation has detected a Sensor transitioned to
non-recoverable from less severe.
May also be shown as 800703011101ffff or 0x800703011101ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0524
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace microprocessor n. (n = microprocessor number)
Appendix A. Integrated management module 2.1 (IMM2.1) error messages
349