4) Remove the caution label for the memory backup battery attached on the top of the EQ100.
Precautions for
Correct Use
- Before using the product, always remove the caution label for the memory backup battery
attached on the top of the EQ100.
* Battery Life
- The battery life is around 5 years (at ambient temperature of 23°C), largely depending on the
operating conditions. This life value is only a reference one and is not guaranteed.
- When a low battery is detected, the device alarm indicator on the EQ100 front end flashes.
Replace the battery within two weeks from the low battery detection.
- Turn off the power before replacing the battery. Attach a new battery within five minutes from
turning off the power. Otherwise the stored data may become indefinite.
* Purchase of New Battery
- For purchase of a new memory backup battery, contact our sales representative.
Product Name
Model
Product Code
Precautions for
Correct Use
- After mounting on a DIN rail or attaching with screws, the EQ100 top cover cannot be opened.
Always attach the battery before mounting.
Precautions
- If you do not use the product for a long period of time, remove the battery. This should prevent
battery consumption and a failure due to leak.
A lithium battery is used for memory backup. Do not
disassemble, apply pressure to deformation, overheat to more
than 100°C, and/or burn it.
Otherwise serious injury may occasionally occur due to fire
and/or explosion.
: Memory backup battery
: CP1W-BAT01
: CP1W-0101E
WARNING
Caution Label of Battery Connection
Cover
5-3