Omron EQ100-E User Manual page 48

Sensor network server
Table of Contents

Advertisement

2. Specifications
Item
SNTP Server
Internal Event Function
Log to Internal
Memory
File Output
Network
Connection Function LAN connection port: Upper level system (EQ server,
Connection
Web UI Function
Taking Out
Internal Data
(1) Collecting by EQ
File
Server
(2) Operation on
Web UI Screen
(3) SD Card Output
(4) FTP transfer
Monitoring
Function
Alarm
Email Notification
Log to Internal
Memory
Status Indication
Device Alarm
Function
Detection
Email Notification
Status Indication
Log to Internal
Memory
A normal event occurrence other than monitoring alarm
and device alarm is collected into the internal memory.
An occurred event is saved into the internal memory. The
event log can be checked on the Web UI screen and
outputted as an event log file.
An event is outputted as an event log file.
EQ-Manager, SMTP server, SNTP server, FTP server,
FTP client), a computer (Web browser), measurement
device
Sub-LAN connection port: Measurement device, computer
(Web browser)
A user can view a status, operate the EQ100, view simple
graph, and perform maintenance through a Web browser
on a computer connected to the LAN or sub-LAN
connection port.
The following four operations are available:
The EQ server collects data and event logs saved in the
EQ100 internal memory via network.
Collected data or event log saved in the EQ100 internal
memory is downloaded by operation on the Web UI
screen.
Any of the following operations outputs collected data and
log files saved in the EQ100 internal memory to an SD
card.
- Pressing SD card save button on the EQ100 front end
- Web UI operation: SD card data output operation
If the SD card output setting is configured as "Yes",
collected data saved in the EQ100 internal memory is
saved on an SD card once a day.
FTP server and FTP client functions are available.
- FTP server function: Acquires collected data files saved
in the EQ100 internal memory via an FTP client and
collected data on an SD card attached to EQ100 or an
event log.
- FTP client function: Sends collected data files saved in
the EQ100 internal memory to the FTP server from
EQ100.
Alarm when collected data exceeds upper or lower limit.
Output to a general-purpose output terminal is available
as well.
Function: Monitoring Alarm Email
An occurred monitoring alarm is saved into the internal
memory. The event log can be checked on the Web UI
screen and outputted as an event log file.
Device alarm indicator is turned on
Detects an instrument failure of EQ100, setup/status,
device, communications, and/or monitoring process.
Function: Device alarm email
Turns on, flashes, long-flashes, or turns temporarily on the
device alarm indicator
An occurred device alarm is saved into the internal
memory. An event can be outputted as an event log file.
Details
2-17

Advertisement

Table of Contents
loading

Table of Contents