7. EQ100 Settings
6) Configure the setup DIP switch SW7 as ON.
SW7=ON
7) If the power of EQ100 is ON, press the reset button for 1 second. Right after then, the
operation status indicator flashes for about 30 seconds (or the power is turned off and on
again).
Reset Button
8) The project setting is written to EQ100.
While the project is being written, the collecting status indicator long-flashes.
Collecting status
9) After writing of the project is completed, the collecting status indicator changes from
long-flashing to short-flashing, and the buzzer is sounded for four seconds.
If the device alarm indicator is on or flashing, a write error occurred. Make sure that the SD
card is properly inserted, that the folder name "EQ_project" is correct, and that the file exists
under the folder.
Collecting status
10) Configure the setup DIP switch SW7 of EQ100 back to OFF.
Precautions for
Correct Use
- You cannot run the product while the setup DIP switch SW7 is ON. Always configure SW7
back to OFF before running the product.
11) Eject the SD card from EQ100 and press the reset button for 1 second.
EQ100 is restarted.
Precautions
- The written project is required to edit the project later for a change of configuration, etc. Keep
it for later edit.
Operation Status
Device Alarm
7-70