Omron EQ100-E User Manual page 245

Sensor network server
Table of Contents

Advertisement

12. Appendix
■Header Block
- Each line of the header block starts with a character "#". The number of lines depends on the
configuration. This section describes information of data for secondary use.
For other output specifications, contact OMRON.
Item
1st line
2nd line
#CHx (x is a number)
#CH:ANNOTATION
#DATE,...
■Data Block
Item
<date>
<time>
L
<measured value [n]>
[n]: repeat count of the number of channel
A timestamp of each data outputted in a CSV file (collected data file) is based on a device with
the shortest cycle among the measurement channels.
A measured value is collected for a channel that successfully collected data. A blank is
collected for a measured value of the time not included in the measurement target.
For a measured value not collected due to communications error, a character string "ERROR"
is outputted.
Communication
Result
Normal
Abnormal
No Communications Blank
e.g.: In case of channel 0 (CH0) = 1 minute cycle, channel 1 (CH1) = 5 minute cycle
(communications error occurred at 00:03:00 in CH0)
2013/06/12,13:00:00.000,L,100,200<LF>
2013/06/12,13:01:00.000,L,100,<LF>
2013/06/12,13:02:00.000,L,100,<LF>
2013/06/12,13:03:00.000,L,ERROR,<LF>
2013/06/12,13:04:00.000,L,100,<LF>
2013/06/12,13:05:00.000,L,100,300<LF>
2013/06/12,13:06:00.000,L,100,<LF>
2013/06/12,13:07:00.000,L,100,<LF>
2013/06/12,13:08:00.000,L,100,<LF>
2013/06/12,13:09:00.000,L,100,<LF>
2013/06/12,13:10:00.000,L,100,400<LF>
This line is always outputted. #OMRON,EQUO,1.5 fixed
This line is always outputted.
SNC_ID is a unique ID for each EQ100.
Channels indicate the number of channels to output
Others are fixed character strings
Indicates channel information. For EQ100, other information than
data type is not used. An internal name corresponding to a data
type indicated as Manager is collected.
A channel name is collected. Names for the number of the
channels are collected.
After this line, the data block starts.
Date of a graph being viewed. Format: YYYY/MM/DD
Time in a format hh:mm:00.000.
"L" is collected (fixed).
A value corresponding to the header of the graph being viewed.
Output Value
A value collected from a
measurement device
"ERROR"
Details
Details
Remarks
e.g.) 99.99
If an operation target of an operation channel
is "ERROR", the operation channel is
"ERROR" as well
-
12-26

Advertisement

Table of Contents
loading

Table of Contents