System Specification - Ametek 2003RP User And Programming Manual

Ac power source
Table of Contents

Advertisement

Parameter
Power Factor

2.4 System Specification

Parameter
Setup storage
Interface
RS-232C
IEEE-488
Remote Inhibit
Function Strobe
Specification
Range
Accuracy
Resolution
Specification
Eight non-volatile front panel setup registers available through
interface. Power-on setting register available from front panel.
(Option package -OP1 required)
Bi-directional serial interface
Handshake:
Data bits:
Stop bits:
Parity:
Baud rate:
Command syntax:
GPIB Interface
IEEE address:
IEEE functions:
Terminators:
Command syntax:
(Option package -OP1 required)
Input
(Option package -OP1 required)
Output
0.00 - 1.00
0.05
0.01
CTS, RTS
8
1
None
19200
IEEE 488.2 commands and SCPI
set using dip switch on rear panel from
0 to 31
SH1, AH1, T6, L3, RL2
LF, CRLF, EOI
IEEE 488.2 commands and SCPI
Contact closure to ground or logic low TTL
signal required to turn off output.
Automatic recovery when RI signal is
removed.
Active low TTL signal. Signal driven low
for approximately 400 sec any time
output voltage or frequency programmed
value changes. Signal level may be
changed by removing jumpers to open
collector.
Unit