3.6 Master Programming Level


When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is
activated and the system Trouble LED flashes until Programming mode is exited. The
following display will appear:
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
The down arrow which appears in the display indicates that additional programming
choices can be viewed by pressing the down arrow key on the keypad. If a down and
up arrow appear in the display, pressing the 'down' arrow key will display the
subsequent Programming Screens as illustrated below while pressing the 'up' arrow
key will display the previous screen.
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
1=HISTORY
2=WALKTEST
3=OPTION MODULES
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK