Setting of the Air to Air Heat Exchanger single operation (Setting
for the header air conditioner)
Single operation of the Air to Air Heat Exchanger is possible when operation of the Air to Air Heat Exchanger is
linked with that of the air conditioners.
Use the
button of the wired remote controller.
* While the Air to Air Heat Exchanger is in operation,
* Adjust this setting for the header air conditioner in the group when an Air to Air Heat Exchanger system linked
with air conditioners is used.
* This setting is invalid when an Air to Air Heat Exchanger(s) system is used.
• Select [31] in step 3 on page 124.
• Select [0001] in step 4 on page 125.
Code
31
Single operation of the fan
REQUIREMENT
Do not change this setting when the operation is linked by a signal from an external device or remotely controlled on
and off (page 119) by using Remote ON/OFF Adapter NRB-1HE (sold separately).
Setting of the imbalanced ventilation Fan speed
SA/EA imbalanced operation of the Air to Air Heat Exchanger is possible.
Use the
button of the remote controller.
* Adjust this setting for all the Air to Air Heat Exchangers when group operation is applied.
* Though RBC-AMT32E, RBC-AMS41E cannot be used, this setting can still be changed. For details, refer to
"Ventilation Fan speed setting" on page 130.
• Select [48] in step 3 on page 124.
• Select [0001: SA (High) > EA (Low) active] or [0002: SA (Low) < EA (High) active] in step 4 on page 125.
Code
Imbalanced ventilation Fan
48
speed
Setting of 24-hour ventilation
24-hour ventilation (intermittent operation of Low mode) is possible.
* Adjust this setting for all the Air to Air Heat Exchangers in the group.
* The air volume of ventilation is half as much as that of Low mode (Ventilated at 60-minute intervals)
* When 24-hour ventilation is in operation, the 24-hour ventilation indicator is not displayed on RBC-AMT32E,
RBC-AMS41E.
• Select [49] in step 3 on page 124.
• Select [0001] in step 4 on page 125.
Code
49
24-hour ventilation
SET DATA
SET DATA
(Factory default)
SET DATA
VENT
is displayed on the remote controller.
0000
Invalid
(Factory default)
0000
Invalid
SA (High) > EA (Low)
0000
Invalid
(Factory default)
128
0001
Valid
0001
0002
SA (Low) < EA (High)
active
active
0001
Valid