Toshiba VN-M150HE Service Manual page 143

Air to air heat exchanger concealed microcomputer control type
Hide thumbs Also See for VN-M150HE:
Table of Contents

Advertisement

Notes for the setting items (Code list: Example)
DN
01
Lighting-up hours of the Filter Sign
02
Extent of filter clogging
03
Central control address
10
Model code
11
Capacity code
14
Group address
28
Auto recovery from a power failure
Ventilation fan speed during 24-hour ventilation/nighttime heat
47
purge operation
48
Unbalanced fan speed ventilation
49
24-hour ventilation
4A
On/off ratio during 24-hour ventilation
4B
Delayed operation
4C
Nighttime heat purge
4D
Setting of the exhausting fan operation below 15°C (0A)
4E
Setting of the linked operation with external devices
5C
Damper output
9D
ON/OFF operation linked with the power status (on/off)
EA
Changing the ventilation mode
EB
Changing the ventilation fan speed
Automatic mode control during linked operation with the air
EC
handling unit
ED
Changing the operation output
EE
Changing the abnormal signal/Bypess mode signal output
* Adjust the setting of EA/EB when using the RBC-AMT 32E, RBC-AMS41E remote controller or using the system without the remote
controller. (Not necessary when using the NRC-01HE remote controller)
Model
Code: 10
Setting
Model
data
Air to Air Heat Exchanger
0050*
(Ceiling-embedded)
* Factory default value of EEPROM installed on the service
circuit board
Item
Model name
(abbreviation)
VN-M***HE series
Memo
Capacity of the Air to Air Heat Exchanger
Code: 11
Setting data
0000*
0001
0002
0003
0004
0005
0006
0007
* Factory default value of EEPROM installed on the service
circuit boar
142
Factory default
0002: 2500H
0000: Normal
0099: Unfixed
0050: Air to Air Heat Exchanger (Ceiling-
embedded duct)
Depending on the capacity
0099: Unfixed
0000: None
0000: Low fixed
0000: Normal
0000: Invalid
0000: Normal
0000: Invalid
0000: Invalid
0000: Exhausting fan run
0000: ON/OFF linked
0000: Normal
0000: Invalid
0003: Automatic mode
0002: High
0000: Valid while the air handling unit is
in operation
0000: ON during normal operation
0000: ON when an abnormal signal is
detected
Type
Invalid
3
150m
/h type
3
250m
/h type
3
350m
/h type
3
500m
/h type
3
650m
/h type
3
800m
/h type
3
1000m
/h type

Hide quick links:

Advertisement

Table of Contents
loading