Toshiba VN-M150HE Service Manual page 139

Air to air heat exchanger concealed microcomputer control type
Hide thumbs Also See for VN-M150HE:
Table of Contents

Advertisement

Check codes and parts to be checked
Wired remote
controller
Main defective parts
display
No header remote
controller
E01
Remote controller
communication error
Remote controller
E02
transmission error
Indoor unit-remote
E03
controller regular
communication error
Duplicated indoor
E08
addresses
Duplicated header
remote controllers
E09
Header indoor unit-indoor
E18
follower unit regular
communication error
Air to Air Heat Exchanger
F17
(TOA) error
Air to Air Heat Exchanger
F18
(TRA) error
Indoor unit, other P.C.
F29
board error
Duplicated header indoor
L03
units
Indoor group address not
L08
set
L09
Indoor power level not set Indoor
LAN communication error Indoor
L20
Other indoor unit error
P31
* "Indoor" in "Judging device" refers to the Air to Air Heat Exchanger or the air conditioner.
Judging
device
Remote
Incorrect remote controller setting --- The header remote
controller
controller has not been set (including two remote controllers).
No signal can be received from the indoor unit.
Remote
System interconnecting wires, indoor P.C. board, remote
controller
controller --- No signal can be sent to the indoor unit.
Indoor
Remote controller, network adapter, indoor P.C. board --- No
data is received from the remote controller or network adapter.
Indoor
Indoor address setting error --- The same address as the self-
address was detected.
Remote
Remote controller address setting error --- Two remote
controller
controllers are set as header in the double-remote controller
control.
(* The header indoor unit stops raising alarm and follower indoor
units continue to operate.)
Indoor
Indoor P.C. board --- Regular communication is not possible
between header and follower indoor units or between twin
header (main) and follower (sub) units.
Air to Air Heat
Outdoor Air sensor (TOA), indoor P.C. board --- Open-circuit or
Exchanger
short-circuit of the heat exchanger sensor (TOA) was detected.
Air to Air Heat
Return Air sensor (TRA), indoor P.C. board --- Open-circuit or
Exchanger
short-circuit of the heat exchanger sensor (TRA) was detected.
Indoor
Indoor P.C. board --- EEPROM error
Indoor
Indoor address setting error --- There are two or more header
units in the group.
Indoor
Indoor address setting error --- Indoor address group has not
been set.
Indoor power level has not been set.
Address setting, central control remote controller, network
adapter --- Duplication of address in central control
communication
Indoor
Another indoor unit in the group is raising an alarm.
E03/L07/L03/L08 alarm check locations and error description
138
Parts to be checked / error description