Ventilation Mode Setting - Toshiba VN-M150HE Service Manual

Air to air heat exchanger concealed microcomputer control type
Hide thumbs

Advertisement

Table of Contents
Setting for linked operation with external devices
Specifies the operation of the Air to Air Heat Exchanger linked with the on/off operation of external devices
* For group operation, adjust this setting for the Air to Air Heat Exchanger to which the Remote ON/OFF Adapter
(NRB-1HE: sold separately) is connected.
• Select [4E] in step 3 on page 124.
• Select a value from the table on the below in step 4 on page 125.
Code
Linked operation with external
4E
devices
0000: The Air to Air Heat Exchanger starts/stops together with the starting/stopping of an external device. (The latter
operation of the remote controller or the switch of the external device overrides the former.)
0001: The Air to Air Heat Exchanger starts together with the starting of an external device. Use the remote controller to
stop operation.
0002: The Air to Air Heat Exchanger stops together with the stopping of an external device. Use the remote controller to
start operation.

Ventilation mode setting

The setting of the ventilation mode can be changed when the remote controller for air conditioners
(RBC-AMT32E, RBC-AMS41E) or a system without a remote controller is used.
* Adjusting this setting is necessary for the header unit when an Air to Air Heat Exchanger system is used (RBC-
AMT32E can not be used.), and for the Air to Air Heat Exchanger with the smallest address number when an Air
to Air Heat Exchanger system linked with air conditioners is used.
* When the remote controller NRC-01HE is installed, this setting is invalid. (The remote controller can be used for
operation.)
• Select [EA] in step 3 on page 124.
• Select a value from the table on the below in step 4 on page 125.
Code
EA
Changing the ventilation mode
Ventilation Fan speed setting
The setting of the ventilation Fan speed can be changed when the remote controller for air conditioners (RBC-
AMT32E, RBC-AMS41E) or the system without the remote controller is used.
* Adjusting this setting is necessary for the header unit when an Air to Air Heat Exchanger system is used (RBC-
AMT32E can not be used.), and for the Air to Air Heat Exchanger with the smallest address number when an Air
to Air Heat Exchanger system linked with air conditioners is used.
* When the remote controller NRC-01HE is installed, this setting is invalid. (The remote controller can be used for
operation.)
• Select [EB] in step 3 on page 124.
• Select a value from the table on the below in step 4 on page 125.
Code
Changing the ventilation
EB
amount
* When [0004] is selected, adjust setting of the imbalanced ventilation Fan speed (Code: 48).
SET DATA
(Factory default)
SET DATA
SET DATA
(Factory default)
0000
ON/OFF linked
0000
Bypass mode
Heat Exchange mode
0002
High
130
0001
ON linked
OFF linked
0001
Automatic mode
(Factory default)
0003
Low
Imbalanced
0002
0002
0004