Model
Code: 10
Setting
Model
data
Air to Air Heat Exchanger
0050*
(Ceiling-embedded)
* Factory default value of EEPROM installed on the service
circuit board
Remote controller switch monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to acquire
temperatures of sensors of indoor unit (Air to Air Heat Exchanger).
1
Push
and
buttons simultaneously for at least 4
seconds to call the service monitor mode.
2
Pushing TEMP.
sensor (CODE No.) to be monitored. (See the following
table.)
3
Pushing
(left side of the button), select an indoor
unit to be monitored.
* The unit number of the Air to Air Heat Exchanger is 31-OO.
4
Push
button to return to the normal display.
Indoor unit data (Air to Air Heat Exchanger)
CODE No.
02
Indoor unit Return air temperature (TRA)
F0
Microcomputer cumulative energized hours (x 100h)
F2
Supply air fan cumulative energized hours (x 100h)
F3
FA
Indoor unit outdoor air temperature (TOA)
Model name
(abbreviation)
VN-M***HE series
buttons, select the number of
Data name
Filter cumulative hours (x1 h)
Capacity of the Air to Air Heat Exchanger
Code: 11
Setting data
0000*
0001
0002
0003
0004
0005
0006
0007
* Factory default value of EEPROM installed on the service
circuit board
2
4
36
Type
Invalid
3
150m
/h type
3
250m
/h type
3
350m
/h type
3
500m
/h type
3
650m
/h type
3
800m
/h type
3
1000m
/h type
1
3