7. Connect the DC power cords.
See
Related Information
"Connect the Chassis Ground Wire" on page 94
■
"Assemble the DC Input Power Cord" on page 95
■
"Connect DC Power Cords" on page 102
■
"Power On the Host for the First Time" on page 103
■
▼ Connect DC Power Cords
1. Prepare the power cords by routing them from the power source to the server.
Note – The server goes into Standby mode and the Oracle ILOM SP initializes as
soon as a power cable connects a power supply to an external power source. System
messages might be lost after 60 seconds if a terminal or terminal emulator is not
connected to the SER MGT port before power is applied.
Note – Oracle ILOM will signal a fault if power is not applied to both supplies
because that situation is a nonredundant condition.
2. Ensure that the input cables are de-energized with no DC power present.
Caution – Do not proceed with these instructions until you are sure that there is no
voltage present on the DC power cables.
3. Route the power cords from the power source to the rear of the server and
secure the cables.
4. Connect the chassis ground wire to the facility ground and ensure that the
connections are properly tightened.
See
5. Connect the -48V or -60V Return and Source wires to the circuit breaker or fuse
panel if they are not already connected.
Caution – Do not turn on the circuit breakers at this time.
102
Netra Server X3-2 Installation Guide • May 2013
"Connect DC Power Cords" on page
"Connect the Chassis Ground Wire" on page
102.
94.