CORNER INSTALLATION USING THE REAR VENT OPTION

NOTE: The horizontal run of vent pipe must be level or have a ¼" rise for every 1' of run toward the termina-
tion. Never allow the vent to run downward. This will cause high temperatures and the possibility of a fire.
USING OFFSETS AND RETURNS: A single 45
maximum 9" horizontal run. NO OTHER ELBOWS OR OFFSETS ARE ALLOWED!
CAUTION: Be sure to maintain 1" air space to any combustibles (2" above horizontal runs). The DXV-35
Fireplace must be installed by a qualified service person.
Mendota recommends the use of Duravent 5"X 8" coaxial pipes and fittings. Duravent components pro-
vide the most flexibility since Duravent horizontal termination caps slide fully over the 6" or 9" straight
pipe section used.
6" LENGTH MINIMUM
9" LENGTH MAXIMUM
FOR 2x4 WALLS, USE THESE DIMENSIONS. FOR 2X6 WALLS, MOVE
FIREPLACE CLOSER TO WALLS IN EACH DIRECTION 2". USE A 9" PIPE
SECTION IF YOU DESIRE A WIDER DIAGONAL MEASUREMENT.
º
4 3/32 FOR 2X4 WALLS
2 19/32 FOR 2X6 WALLS
44 29/32
64 5/32
45 Deg L
ADJUSTABLE
4 3/32 FOR 2X4 WALLS
2 19/32 FOR 2X6 WALLS
horizontal elbow is already calculated into the allowable
44 29/32
27
10 13/16
6" PIPE MINIMUM REQ'D
9" PIPE MAXIMUM ALLOWED
45 DEG.
ELBOW