Note: Make sure that the distance is between 0.5" to 1" greater than the distance you
measured between the two vertical rack rails to allow adjustment at a later stage.

Figure 31: Positioning and aligning the mounting bar and long bracket

Total distance = rack measurements + 0.5 to 1" for adjustment.
4. Secure the rail on the side of the switch using two 8-32x1/4" pan head Philips screws (use
the holes on the top row). Make sure you install one screw in the middle of the switch and
the other screw at the edge (use the holes on the top row of the rail).

Figure 32: Securing the rail

5. Ensure that the clip nuts are already installed in the rack holes of the correct U level (on all
four vertical rack rails) as described in
(on page 33).
44
Measuring the Distance between Mounting Rails
Hardware Installation