Managing temperature settings
TABLE 17
Model
ICX 6430-48P
ICX 6450-24
ICX 6450-24P
ICX 6450-48
ICX 6450-48P
Changing the temperature warning level
To change the temperature at which the device sends a syslog message and an SNMP trap, enter a
command similar to the following at the Privileged EXEC level of the CLI.
Brocade# temperature warning 1 85
Syntax: temperature warning stack-id value
The stack-id can be a value from 1 through 8.
The value variable is the temperature warning level, in Celsius. You cannot set this level higher than
83°C
temperature shut down level, which is automatically set by the device.
The following console and syslog message is displayed when the temperature reaches the warning
level:
!!! Temperature is over warning level on stack unit 1!!!
Temperature shutdown levels
When the temperature crosses the critical (shutdown) threshold levels, the device will reset after 5
minutes. The following console and syslog message is displayed:
!!! Temperature is over shutdown level, please shutdown your stack unit 1 to avoid
hw damage!!!
NOTE
Brocade recommends that you shut down your stack unit to avoid any hardware damage.
Changing the temperature poll time
By default, the software polls the temperature sensor every 60 seconds to get the current
temperature. This poll rate is controlled by the device poll time, which also controls how often the
software polls other system components.
To change the poll time, enter a command similar to the following at the global CONFIG level.
Brocade(config)# chassis poll-time 200
Syntax: chassis poll-time value
70
Temperature thresholds
Low limit temperature
TA (
°C)
58
66
59
64
56
. The temperature warning level must be at least five degrees Celsius less than the
Brocade ICX 6430 and ICX 6450 Stackable Switches Hardware Installation Guide
High limit temperature
Critical (shutdown)
TB (
temperature
°C)
TC (
63
79
71
83
64
88
69
76
61
79
°C)
53-1002738-02