Project Explorer dialog in the Communication Engineering Tool window
4.6.
Ethernet Adapter
Installation and Commissioning Manual

Configuring SPA-ZC 400 using imported CID file

If you have to configure several SPA-ZC 400 with the similar IEC 61850 data object
model, it is possible to import a previously generated CID file and change the
communication addresses, typically by changing the IP address.
Add the project and the logical device LD0 like in Section 4.4. Configuring SPA-
ZC 400 by using Connectivity Packages. Add a logical device to the SPA-ZC 40x
Device object by right-clicking to select SPA-ZC 40x > New > Communication >
Logical Device.You have to select the CID Import function by choosing a new
empty logical node and then right-click to select the CID Import function.
In the CID Import dialog you can select the right CID file from the workstation
directory and import it to a previously created logical node. LD0 contains the data
sets and reporting control blocks. Other logical devices describe the data model of a
connected IED.
SPA-ZC 400
A040026