Step Position With Transient Indication; Originator - ABB SPA-ZC 400 Installation And Commissioning Manual

Ethernet adapter
Table of Contents

Advertisement

SPA-ZC 400
7.3.1.5.
Table 7.3.1.5-1 Step position with transient indication
ValWithTrans Type Definition
Attribute Name
posVal
transInd
7.3.2.
Table 7.3.2-1

Step position with transient indication

OriginatorType Definition
Attribute Name
orCat
orIdent
Table 7.3.2-2
Values for orCat
Value
bay-control
station-control
remote-control
automatic-bay
automatic-station
automatic-remote
maintenance
process
68
Ethernet Adapter
Installation and Commissioning Manual
Step position with transient indication
AttributeType
Value/ Value Range
INT8
-64 ... 63
BOOLEAN

Originator

AttributeType
Value/ Value Range
ENUMERATED
not-supported | bay-
control | station-
control | remote-
control | automatic-
bay | automatic-
station | automatic-
remote | maintenance
| process
OCTET STRING64
Explanation
Control operation issued from an operator using a client located at bay level
Control operation issued from an operator using a client located at station level
Control operation from a remote operater outside the substation (e.g. network control center)
Control operation issued from an automatic function at bay level
Control operation issued from an automatic function at station level
Control operation issued from an automatic function outside of the substation
Control operation issued from a maintenance / service tool
Status change occurred without control action (e.g. external trip of a circuit breaker or failure
inside the breaker)
M/O/C
SPA-ZC 400/
Comments
M
Supported
O
Not Supported
M/O/C
SPA-ZC 400/
Comments
M
Supported
M
Supported
1MRS755347