Commissioning Spa-Zc 400; Checking Spa Communication - ABB SPA-ZC 400 Installation And Commissioning Manual

Ethernet adapter
Table of Contents

Advertisement

1MRS755347
4.12.
4.12.1.
Ethernet Adapter
Installation and Commissioning Manual

Commissioning SPA-ZC 400

The downloaded CID file is taken into use when restarting SPA-ZC 400.
Normally, the reset happens automatically after the configuration is downloaded
with Communication Engineering Tool.
You can see how the configuration process is progressing from the diagnostic LEDs.
When the SPA-ZC 400 configuration is completed, then the green LED is on. If
SPA-ZC 400 is online with the IEC 61850 client, you can check the general
configuration status of SPA-ZC 400 from the data model LD0.LLN0.Health.stVal:
1. OK, configuration is completed succesfully.
2. Warning, no clock synchronization.
3. Alarm, during the configuration appeared errors.
If the configuration fails, first you should check the error log files from the
SPA-ZC 400 file system.The status and error logs locate in the /log directory.

Checking SPA communication

In case the configuration is completes succesfully, you can check the resetable
diagnostic counters through the IEC 61850 data model or SPA-ZC 400 file system.
SPA-ZC 400 Diagnostic counters are part of the LD0.LLN0.Mod attributes. The
data object type is ABB specific extension in IEC 61850 data model and contains
the counters as data attibutes. It is possible to reset the counters by writing 1 into
ctlVal. It is not recommended to put the counters into the data set because the
counter values are updated only during a read operation.
Fig. 4.12.1.-1 Diagnostic counters
SPA-ZC 400
A040136
51