1MRS755347
Fig. 4.8.-1 Communication Parameters
4.8.1.
Ethernet Adapter
Installation and Commissioning Manual

SPA Communication parameters

SPA-ZC 400 needs also IED SPA address to access the SPA data. Every logical
device has SPA Communication Parameters Object properties expect LD0, which
describes the SPA-ZC 400. The SPA Address object property has to be the same as
the configured SPA unit number in IED.
SPA-ZC 400 has to know the SPA Password to write the data to IED.
Password (SPA parameter 0V160) is needed only for controllable
integer status (INC). The SPA Password has to be same as defined in
IED MMI.
SPA-ZC 400 uses default bit rate 9600 bits/s. Other possible values are 1200, 2400,
4800, 9600 and 19200 bits/s. Used value has to be same as the configured value in
IED.
SPA-ZC 400 has three different modes of the IED time synchronization. The mode
is selected from the logical device object describing the IED, for example LD1.
SPA-ZC 400
A040022
45