1MRS755347
7.3.3.18.
Table 7.3.3.18-1 Controllable double point (DPC)
SPC class
Attribute
Attribute
Name
Type
DataName
Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
ctlVal
BOOLEAN
operTm
TimeStamp
origin
Originator
ctlNum
INT8U
stVal
CODED ENUM
q
Quality
t
TimeStamp
stSeld
BOOLEAN
subEna
BOOLEAN
subVal
CODED ENUM
subQ
Quality
subID
VISIBLE STRING64
pulseConfi
PulseConfig
g
ctlModel
ENUMERATED
sboTimeout
INT32U
sboClass
ENUMERATED
Ethernet Adapter
Installation and Commissioning Manual
Controllable double point (DPC)
The table below defines the common data class of controllable double point.
FC
TrgOp
Control and Status
CO
CO
CO
ST
CO
ST
ST
dchg
ST
qchg
ST
ST
dchg
Substitution
SV
SV
SV
SV
Configuration, Description and Extension
CF
CF
CF
CF
Value/
Value range
off (FALSE) | on (TRUE)
0..255
intermediate-state | off | on |
bad-state
intermediate-state | off | on |
bad-state
status-only | direct-with-
normal-security | sbo-with-
normal-security | direct-with-
enhanced-security | sbo-
with-enhanced-security
operate-once (0) | operate-
many (1)
SPA-ZC 400
M/O/C
SPA-ZC 400/
Comments
Supported
AC_CO_M
Supported
AC_CO_O
Not Supported
AC_CO_O
Supported
AC_CO_O
Supported
M
Supported
M
Supported
M
Supported
AC_CO_O
Supported
PICS_SUBST
Not Supported
PICS_SUBST
Not Supported
PICS_SUBST
Not Supported
PICS_SUBST
Not Supported
AC_CO_O
Not Supported
M
Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported