Configuring SPA-ZC 400 using IEC 61850 data model
components
You can configure the IED model from the beginning. You have to be familiar with
the IED, SPA model and how the IED model can be converted to the IEC 61850
model. If this configuration method is used, it is recommended that you familiarize
yourself with Connectivity Packages as an example. Contact ABB if you have
unresolved problems.
You can start building the IEC 61850 data model by creating an empty logical
device, see Section 4.5.2. Adding Logical Device objects. The IEC 61850 standard
defines a mandatory logical node LLN0 for every device and for its objects. You can
add a logical node (LN) with the LN wizard tool, see Fig. 4.7.-1. You can open a
logical node by right-clicking the respective logical device. You have to choose the
logical node type and add a unique instance number for the logical node type.
A prefix is an additional naming parameter for a logical node.
Fig. 4.7.-1 LN wizard
When the logical node is ready, you have to define data objects (DO) to it. You can
add data objects with DO Wizard, see Fig. 4.7.-2. You can open the logical node by
right-clicking the logical device. You have to choose the data object type and give a
unique name within the selected logical node. DO Wizard has a set of pre-defined
data objects with hard-coded data attributes. For more information on data objects,
refer to Section 7.3. Model conformance statement.
1MRS755347
A040131