Scl Control Block - ABB SPA-ZC 400 Installation And Commissioning Manual

Ethernet adapter
Table of Contents

Advertisement

SPA-ZC 400
Table 7.4.-3
Additional MMS services for SCL.2 and SCL.3
SCL conformance
MMS Services
GetCapabilityList
GetDomainAttributes
LoadDomain
StoreDomain
a. Must be m if support SCL.3 is declared.
b. Must be m if support for remote creation of a SCL is declared.
7.5.
Table 7.5.-1
Definition of SCL control block
IEC 61850-8-1
MMS
Component Name
TypeDescription
validate
VISIBLE-STRING
size of 64 octets
valState
Unsigned Integer -
8 bits
activate
VISIBLE-STRING
size of 64 octets
100
Ethernet Adapter
Installation and Commissioning Manual
The additional MMS services, defined table below, must be supported if support for
SCL.2 or SCL.3 is declared.
Client-CR
Base
F/S
O
O
O
O
b

SCL control block

The SCL control block must have a functional constraint of SC. This control block
must occur in LLN0 only.
The SCL control block must be a structured MMS type definition that contains the
ordered named components defined in the table below.
r/w
r
w
r
r
w
Value/Range
i
o
a
m/o
Comments
m
Must be m if support for remote
o
activation of an SCL is declared.
m
(0) - NOT-VALIDATED
(1) - VALIDATION-ERROR
(2) - VALIDATED
(3) - VALIDATION-IN-
PROGRESS
(4) - NOT-SUPPORTED
(5) - VALIDATE-FILE-PRESENT
m
Must be m if support for remote
o
activation of an SCL is declared.
1MRS755347
Server-CR
Base
F/S
SPA-ZC 400/
Comments
Not Supported
o
i
Not Supported
o
m
Not Supported
o
Not Supported
a
o
Not Supported
b
SPA-ZC 400/
Comments
N/A for TP client
N/A for TP client
N/A for TP client